The Safe torque off function 201
Cable types and lengths
Double-shielded twisted-pair cable is recommended.
Maximum cable lengths:
300 m (984 ft) between activation switch [K] and drive control unit
60 m (200 ft) between multiple drives
60 m (200 ft) between external power supply and first drive.
Note: The voltage at the INx terminals of each drive control unit must be at least 17 V DC
to be interpreted as “1”.
Grounding of protective shields
Ground the shield in the cabling between the activation switch and the control unit at
the control unit.
Ground the shield in the cabling between two control units at one control unit only.