Parameters 151
10.13 DI5 ON delay Defines the activation delay for digital input DI5. 0.0 s
t
On
= 10.13 DI5 ON delay
t
Off
= 10.14 DI5 OFF delay
*Electrical status of digital input. Indicated by 10.01 DI status.
**Indicated by 10.02 DI delayed status.
0.0 … 3000.0 s Activation delay for DI5. 10 = 1 s
10.14 DI5 OFF delay Defines the deactivation delay for digital input DI5. See
parameter 10.13 DI5 ON delay.
0.0 s
0.0 … 3000.0 s Deactivation delay for DI5. 10 = 1 s
10.15 DI6 ON delay Defines the activation delay for digital input DI6. 0.0 s
t
On
= 10.15 DI6 ON delay
t
Off
= 10.16 DI6 OFF delay
*Electrical status of digital input. Indicated by 10.01 DI status.
**Indicated by 10.02 DI delayed status.
0.0 … 3000.0 s Activation delay for DI6. 10 = 1 s
10.16 DI6 OFF delay Defines the deactivation delay for digital input DI6. See
parameter 10.15 DI6 ON delay.
0.0 s
0.0 … 3000.0 s Deactivation delay for DI6. 10 = 1 s
10.21 RO status Status of relay outputs RO8…RO1. Example: 00000001b =
RO1 is energized, RO2…RO8 are de-energized.
-
0000h…FFFFh Status of relay outputs. 1 = 1
10.24 RO1 source Selects a drive signal to be connected to relay output RO1. Ready run;
10.01 b3 (-1)
(95.20 b2);
35.105 b1
(95.20 b6);
06.16 b6
(95.20 b9)
Not energized Output is not energized. 0
Energized Output is energized. 1
Ready run Bit 1 of 06.11 Main status word (see page 131). 2
No. Name/Value Description Def/FbEq16
1
0
1
0
t
On
t
Off
t
On
t
Off
*DI status
**Delayed DI status
Time
1
0
1
0
t
On
t
Off
t
On
t
Off
*DI status
**Delayed DI status
Time