170 Parameters
Remote control Bit 9 of 06.11 Main status word (see page 131). 24
Supervision 1 Bit 0 of 32.01 Supervision status (see page 282). 33
Supervision 2 Bit 1 of 32.01 Supervision status (see page 282). 34
Supervision 3 Bit 2 of 32.01 Supervision status (see page 282). 35
RO/DIO control
word bit0
Bit 0 of 10.99 RO/DIO control word (see page 154). 40
RO/DIO control
word bit1
Bit 1 of 10.99 RO/DIO control word (see page 154). 41
RO/DIO control
word bit2
Bit 2 of 10.99 RO/DIO control word (see page 154). 42
RO/DIO control
word bit8
Bit 8 of 10.99 RO/DIO control word (see page 154). 43
RO/DIO control
word bit9
Bit 9 of 10.99 RO/DIO control word (see page 154). 44
Other [bit] Source selection (see Terms and abbreviations on page 114). -
14.12 DI1 ON delay (Visible when 14.01 Module 1 type = FDIO-01)
Defines the activation delay for digital input DI1.
0.00 s
t
On
= 14.12 DI1 ON delay
t
Off
= 14.13 DI1 OFF delay
*Electrical status of DI or status of selected source (in output mode). Indicated by 14.05 DI status.
**Indicated by 14.06 DI delayed status.
0.00 … 3000.00 s Activation delay for DI1. 10 = 1 s
14.12 DIO1 ON delay (Visible when 14.01 Module 1 type = FIO-01 or FIO-11)
Defines the activation delay for digital input/output DIO1.
0.00 s
t
On
= 14.12 DIO1 ON delay
t
Off
= 14.13 DIO1 OFF delay
*Electrical status of DIO (in input mode) or status of selected source (in output mode). Indicated by 14.05 DIO status.
**Indicated by 14.06 DIO delayed status.
0.00 … 3000.00 s Activation delay for DIO1. 10 = 1 s
No. Name/Value Description Def/FbEq16
1
0
1
0
t
On
t
Off
t
On
t
Off
*DI status
**Delayed DI status
Time
1
0
1
0
t
On
t
Off
t
On
t
Off
*DIO status
**Delayed DIO status
Time