EasyManua.ls Logo

ABB ACS880-17 - Page 267

ABB ACS880-17
604 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameters 267
30.19 Minimum torque 1 Defines a minimum torque limit for the drive (in percent of
nominal motor torque). See diagram at parameter 30.18
Minimum torque sel.
The limit is effective when
the source selected by 30.18 Minimum torque sel is 0, or
30.18 is set to Minimum torque 1.
Note: Do not set this parameter to 0% in an attempt to prevent
reverse rotation. In an open-loop application, that is likely to
prevent the motor from stopping altogether. To prevent
reverse rotation, use the speed/frequency limits in this
parameter group, or parameters 20.23/20.24.
-300.0%
-1600.0 … 0.0% Minimum torque limit 1. See par.
46.03
30.20 Maximum torque 1 Defines a maximum torque limit for the drive (in percent of
nominal motor torque). See diagram at parameter 30.18
Minimum torque sel.
The limit is effective when
the source selected by 30.25 Maximum torque sel is 0, or
30.25 is set to Maximum torque 1.
300.0%
0.0 … 1600.0% Maximum torque 1. See par.
46.03
30.21 Minimum torque 2
source
Defines the source of the minimum torque limit for the drive (in
percent of nominal motor torque) when
the source selected by parameter 30.18 Minimum torque
sel is 1, or
30.18 is set to Minimum torque 2 source.
See diagram at 30.18 Minimum torque sel.
Note: Any positive values received from the selected source
are inverted.
Minimum
torque 2
Zero None. 0
AI1 scaled 12.12 AI1 scaled value (see page 161). 1
AI2 scaled 12.22 AI2 scaled value (see page 162). 2
PID 40.01 Process PID output actual (output of the process PID
controller).
5
Minimum torque 2 30.23 Minimum torque 2.6
Other
Source selection (see Terms and abbreviations on page 114). -
30.22 Maximum torque 2
source
Defines the source of the maximum torque limit for the drive
(in percent of nominal motor torque) when
the source selected by parameter 30.25 Maximum torque
sel is 1, or
30.25 is set to Maximum torque 2 source.
See diagram at 30.18 Minimum torque sel.
Note: Any negative values received from the selected source
are inverted.
Maximum
torque 2
Zero None. 0
AI1 scaled 12.12 AI1 scaled value (see page 161). 1
AI2 scaled 12.22 AI2 scaled value (see page 162). 2
PID 40.01 Process PID output actual (output of the process PID
controller).
5
Maximum torque 2 30.24 Maximum torque 2.6
Other Source selection (see Terms and abbreviations on page 114). -
No. Name/Value Description Def/FbEq16

Table of Contents

Other manuals for ABB ACS880-17

Related product manuals