Parameters 303
35.102 DOL starter off
delay
Defines a stop delay for the motor fan.
The delay timer starts when the control source selected by
parameter 35.100 switches off. After the delay, bit 1 of 35.105
switches off.
20 min
0…715828 min Motor fan stop delay. 1 = 1 min
35.103 DOL starter
feedback source
Selects the input for motor fan feedback signal.
0 = Stopped
1 = Running
After the fan is started (bit 1 of 35.105 switches on), feedback
is expected within the time set by 35.104.
Not selected;
DI5
(95.20 b6)
Not selected 0. 0
Selected 1. 1
DI1 Digital input DI1 (10.02 DI delayed status, bit 0). 2
DI2 Digital input DI2 (10.02 DI delayed status, bit 1). 3
DI3 Digital input DI3 (10.02 DI delayed status, bit 2). 4
DI4 Digital input DI4 (10.02 DI delayed status, bit 3). 5
DI5 Digital input DI5 (10.02 DI delayed status, bit 4). 6
DI6 Digital input DI6 (10.02 DI delayed status, bit 5). 7
DIO1 Digital input/output DIO1 (11.02 DIO delayed status, bit 0). 10
DIO2 Digital input/output DIO2 (11.02 DIO delayed status, bit 1). 11
Other [bit] Source selection (see Terms and abbreviations on page 114). -
35.104 DOL starter
feedback delay
Defines a feedback delay for the motor fan.
The delay timer starts when bit 1 of 35.105 switches on. If no
feedback is received from the fan until the delay elapses, the
action selected by 35.106 is taken.
Note: This delay is only applied at start. If the feedback signal
is lost during run, the action selected by 35.106 is taken
immediately.
0 s; 5 s
(95.20 b6)
0…42949673 s Motor fan start delay. 1 = 1 s
No. Name/Value Description Def/
FbEq16