306 Parameters
36.08 Logger function Determines whether amplitude loggers 1 and 2 are active
continuously or only when the drive is modulating.
-
0000b…0011b Amplitude logger activity selection. 1 = 1
36.09 Reset loggers Resets the peak value logger and/or amplitude logger 2.
(Amplitude logger 1 cannot be reset.)
Done
Done Reset completed or not requested (normal operation). 0
All Reset both the peak value logger and amplitude logger 2. 1
PVL Reset the peak value logger. 2
AL2 Reset amplitude logger 2. 3
36.10 PVL peak value Displays the peak value recorded by the peak value logger. 0.00
-32768.00 …
32767.00
Peak value. 1 = 1
36.11 PVL peak date Displays the date on which the peak value was recorded. -
- Peak occurrence date. -
36.12 PVL peak time Displays the time at which the peak value was recorded. -
- Peak occurrence time. -
36.13 PVL current at peak Displays the motor current at the moment the peak value was
recorded.
0.00 A
-32768.00 …
32767.00 A
Motor current at peak. 1 = 1 A
36.14 PVL DC voltage at
peak
Displays the voltage in the intermediate DC circuit of the drive
at the moment the peak value was recorded.
0.00 V
0.00 … 2000.00 V DC voltage at peak. 10 = 1 V
36.15 PVL speed at peak Displays the motor speed at the moment the peak value was
recorded.
0.00 rpm
-32768.00 …
32767.00 rpm
Motor speed at peak. See par.
46.01
36.16 PVL reset date Displays the date on which the peak value logger was last
reset.
-
- Last reset date of the peak value logger. -
36.17 PVL reset time Displays the time at which the peak value logger was last
reset.
-
- Last reset time of the peak value logger. -
36.20 AL1 below 10% Displays the percentage of samples recorded by amplitude
logger 1 that were below 10%. Note that this percentage also
includes the samples that had a negative value.
0.00%
0.00 … 100.00% Amplitude logger 1 samples below 10%. 1 = 1%
No. Name/Value Description Def/FbEq16
Bit Name Description
0 AL1 0 = Amplitude logger 1 active continuously
1 = Amplitude logger 1 active only when the drive is modulating
1 AL2 0 = Amplitude logger 2 active continuously
1 = Amplitude logger 2 active only when the drive is modulating
2…15 Reserved