Parameters 315
40.19 Set 1 internal
setpoint sel1
Selects, together with 40.20 Set 1 internal setpoint sel2, the
internal setpoint out of the presets defined by parameters
40.2140.24.
Not selected
Not selected 0. 0
Selected 1. 1
DI1 Digital input DI1 (10.02 DI delayed status, bit 0). 2
DI2 Digital input DI2 (10.02 DI delayed status, bit 1). 3
DI3 Digital input DI3 (10.02 DI delayed status, bit 2). 4
DI4 Digital input DI4 (10.02 DI delayed status, bit 3). 5
DI5 Digital input DI5 (10.02 DI delayed status, bit 4). 6
DI6 Digital input DI6 (10.02 DI delayed status, bit 5). 7
DIO1 Digital input/output DIO1 (11.02 DIO delayed status, bit 0). 10
DIO2 Digital input/output DIO2 (11.02 DIO delayed status, bit 1). 11
Other [bit] Source selection (see Terms and abbreviations on page 114). -
40.20 Set 1 internal
setpoint sel2
Selects, together with 40.19 Set 1 internal setpoint sel1, the
internal setpoint out of the presets defined by parameters
40.2140.24. See table at 40.19 Set 1 internal setpoint sel1.
Not selected
Not selected 0. 0
Selected 1. 1
DI1 Digital input DI1 (10.02 DI delayed status, bit 0). 2
DI2 Digital input DI2 (10.02 DI delayed status, bit 1). 3
DI3 Digital input DI3 (10.02 DI delayed status, bit 2). 4
DI4 Digital input DI4 (10.02 DI delayed status, bit 3). 5
DI5 Digital input DI5 (10.02
DI delayed status, bit 4). 6
DI6 Digital input DI6 (10.02 DI delayed status, bit 5). 7
DIO1 Digital input/output DIO1 (11.02 DIO delayed status, bit 0). 10
DIO2 Digital input/output DIO2 (11.02 DIO delayed status, bit 1). 11
Other [bit] Source selection (see Terms and abbreviations on page 114). -
40.21 Set 1 internal
setpoint 1
Defines process setpoint preset 1. See parameter 40.19 Set 1
internal setpoint sel1.
The unit is selected by parameter 40.12 Set 1 unit selection.
0.00
-32768.00 …
32767.00
Process setpoint preset 1. 1 = 1 unit
40.22 Set 1 internal
setpoint 2
Defines process setpoint preset 2. See parameter 40.19 Set 1
internal setpoint sel1.
The unit is selected by parameter 40.12 Set 1 unit selection.
0.00
-32768.00 …
32767.00
Process setpoint preset 2. 1 = 1 unit
No. Name/Value Description Def/FbEq16
Source defined
by par. 40.19
Source defined
by par. 40.20
Setpoint preset active
0 0 1 (par. 40.21)
1 0 2 (par. 40.22)
0 1 3 (par. 40.23)
1 1 4 (par. 40.24)