Parameters 399
91.06 Module 2
temperature
Displays the temperature measured through the sensor input
of interface module 2. The unit is selected by parameter 96.16
Unit selection.
Note: With a PTC sensor, the unit is ohms.
This parameter is read-only.
-
0…1000 °C, °F or
ohm
Temperature measured through interface module 2. -
91.10 Encoder parameter
refresh
Validates any changed encoder interface module parameters.
This is needed for any parameter changes in groups 90…93
to take effect.
After refreshing, the value reverts automatically to Done.
Notes:
• Permanent magnet motors only: The drive will perform a
fresh autophasing routine (see page 59) at next start if the
motor feedback encoder settings have been changed.
• The parameter cannot be changed while the drive is
running.
Done
Done Refreshing done. 0
Refresh Refreshing. 1
91.11 Module 1 type Defines the type of the module used as interface module 1. None
None None (communication disabled). 0
FEN-01 FEN-01. 1
FEN-11 FEN-11. 2
FEN-21 FEN-21. 3
FEN-31 FEN-31. 4
FSE-31 FSE-31. 5
91.12 Module 1 location Specifies the slot (1…3) on the control unit of the drive into
which the interface module is installed. Alternatively, specifies
the node ID of the slot on an FEA-03 extension adapter.
Slot 2
Slot 1 Slot 1. 1
Slot 2 Slot 2. 2
Slot 3 Slot 3. 3
4…254 Node ID of the slot on the FEA-03 extension adapter. 1 = 1
91.13 Module 2 type Defines the type of the module used as interface module 2. None
None None (communication disabled). 0
FEN-01 FEN-01. 1
FEN-11 FEN-11. 2
FEN-21 FEN-21. 3
FEN-31 FEN-31. 4
FSE-31 FSE-31. 5
91.14 Module 2 location Specifies the slot (1…3) on the control unit of the drive into
which the interface module is installed. Alternatively, specifies
the node ID of the slot on an FEA-03 extension adapter.
Slot 3
Slot 1 Slot 1. 1
Slot 2 Slot 2. 2
Slot 3 Slot 3. 3
4…254 Node ID of the slot on the FEA-03 extension adapter. 1 = 1
No. Name/Value Description Def/FbEq16