Parameters 417
95.21 HW options word 2 Specifies more hardware-related options that require
differentiated parameter defaults. See parameter 95.20 HW
options word 1.
WARNING! After switching any bits in this word,
recheck the values of the affected parameters.
Note: This parameter cannot be changed while the drive is
running.
-
0000h…FFFFh Hardware options configuration word 2. 1 = 1
95.30 Parallel type list
filter
(Only visible with a BCU control unit)
Filters the list of drive/inverter types listed by parameter 95.31
Parallel type configuration.
Note: This parameter cannot be changed while the drive is
running.
No filter
No filter All types listed. 1
-3 (380-415V) -3 (380…415 V) types listed. 2
-5 (380-500V) -5 (380…500 V) types listed. 3
-7 (525-690V) -7 (525…690 V) types listed. 4
-7 LC (525-690V) Liquid-cooled -7 (525…690 V) types listed. 5
95.31 Parallel type
configuration
(Only visible with a BCU control unit)
Defines the drive/inverter type if it consists of parallel-
connected modules.
If the drive/inverter consists of a single module, leave the
value at Not selected.
Note: This parameter cannot be changed while the drive is
running.
Not selected
Not selected The drive/inverter does not consist of parallel-connected
modules, or type not selected.
0
[Drive/inverter type] Drive/inverter type consisting of parallel-connected modules. -
95.40 Transformation ratio Defines the ratio of the step-up transformer. 0.000
0.000 … 100.000 Step-up transformer ratio. 1000 = 1
No. Name/Value Description Def/FbEq16
Bit Name Information
0 Dual use 1 = Dual use active. For drives with option +N8200. (Allows higher
output speeds/frequencies and speed/frequency reference limits.)
1 SynRM 1 = Synchronous reluctance motor used. Affects parameters 25.02,
25.03, 25.15, 99.03.
2 Salient PM 1 = Salient-pole permanent magnet motor used. Affects parameters
25.02, 25.03, 25.15, 99.03.
3 LV Synchro 1 = Externally-excited synchronous motor used. Requires a license.
Contact your local ABB representative for more information.
4 Aux fan 1
supervision
1 = Auxiliary fan 1 installed and supervised.
5 Aux fan 2
supervision
1 = Auxiliary fan 2 installed and supervised.
6…15 Reserved