420 Parameters
FIELDBUS Reserved. 6
96.05 Macro active Shows which application macro is currently selected. See
chapter Application macros (page 97) for more information.
To change the macro, use parameter 96.04 Macro select.
Factory
Factory Factory macro (see page 98). 1
Hand/Auto Hand/Auto macro (see page 100). 2
PID-CTRL PID control macro (see page 102). 3
T-CTRL Torque control macro (see page 106). 4
Sequence control Sequential control macro (see page 108). 5
FIELDBUS Fieldbus control macro (see page 111). 6
96.06 Parameter restore Restores the original settings of the control program, ie.
parameter default values.
Note: This parameter cannot be changed while the drive is
running.
Done
Done Restoring is completed. 0
Restore defaults All editable parameter values are restored to default values,
except
• motor data and ID run results
• parameter 31.42 Overcurrent fault limit
• control panel/PC communication settings
• I/O extension module settings
• fieldbus adapter settings
• encoder configuration data
• application macro selection and the parameter defaults
implemented by it
• parameter 95.01 Supply voltage
• parameter 95.09 Switch fuse controller
• differentiated defaults implemented by parameters 95.20
HW options word 1 and 95.21 HW options word 2
• user lock configuration parameters 96.100…96.102.
8
Clear all All editable parameter values are restored to default values,
except
• control panel/PC communication settings
• application macro selection and the parameter defaults
implemented by it
• parameter 95.01 Supply voltage
• parameter 95.09 Switch fuse controller
• differentiated defaults implemented by parameters 95.20
HW options word 1 and 95.21 HW options word 2
• user lock configuration parameters 96.100…96.102.
PC tool communication is interrupted during the restoring.
Note: Activating this selection will restore the default settings
of the fieldbus adapter if one is connected, potentially
including settings that cannot be accessed through drive
parameters.
62
Reset all fieldbus
settings
Fieldbus adapter and embedded fieldbus interface settings
(parameter groups 50…58) are restored to default values.
This will also restore the default settings of the fieldbus
adapter if one is connected, potentially including settings that
cannot be accessed through drive parameters.
32
No. Name/Value Description Def/FbEq16