424 Parameters
96.24 Full days since 1st
Jan 1980
Number of full days passed since beginning of the year 1980.
This parameter, together with 96.25 Time in minutes within 24
h and 96.26 Time in ms within one minute makes it possible to
set the date and time in the drive via the parameter interface
from a fieldbus or application program. This may be
necessary if the fieldbus protocol does not support time
synchronization.
-
1…59999 Days since beginning of 1980. 1 = 1
96.25 Time in minutes
within 24 h
Number of full minutes passed since midnight. For example,
the value 860 corresponds to 2:20 pm.
See parameter 96.24 Full days since 1st Jan 1980.
0 min
1…1439 Minutes since midnight. 1 = 1
96.26 Time in ms within
one minute
Number of milliseconds passed since last minute.
See parameter 96.24 Full days since 1st Jan 1980.
0 ms
0…59999 Number of milliseconds since last minute. 1 = 1
96.29 Time sync source
status
Time source status word.
This parameter is read-only.
-
0000h…FFFFh Time source status word 1. 1 = 1
No. Name/Value Description Def/FbEq16
Bit Name Description
0 Time tick
received
1 = 1st priority tick received: Tick has been received from 1st priority
source (or from 96.24…96.26).
1Aux Time
tick received
1 = 2nd priority tick received: Tick has been received from 2nd priority
source.
2Tick interval
is too long
1 = Yes: Tick interval too long (accuracy compromised).
3 DDCS
controller
1 = Tick received: Tick has been received from an external controller.
4Master/
Follower
1 = Tick received: Tick has been received through the master/follower link.
5 Reserved
6 D2D 1 = Tick received: Tick has been received through the drive-to-drive link.
7 FbusA 1 = Tick received: Tick has been received through fieldbus interface A.
8 FbusB 1 = Tick received: Tick has been received through fieldbus interface B.
9 EFB 1 = Tick received: Tick has been received through the embedded fieldbus
interface.
10 Reserved.
11 Panel link 1 = Tick received: Tick has been received from the control panel, or Drive
composer PC tool connected to the control panel.
12 Ethernet tool
link
1 = Tick received: Tick has been received from Drive composer PC tool
through an FENA module.
13 Parameter
setting
1 = Tick received: Tick has been set by parameters 96.24…96.26.
14 RTC 1 = RTC time in use: Time and date have been read from the real-time
clock.
15 Drive On-
Time
1 = Drive on-time in use: Time and date are displaying drive on-time.