516 Fault tracing
A981 External warning 1
(Editable message text)
Programmable warning:
31.01 External event 1
source
31.02 External event 1
type
Fault in external device 1. Check the external device.
Check setting of parameter 31.01
External event 1 source.
A982 External warning 2
(Editable message text)
Programmable warning:
31.03 External event 2
source
31.04 External event 2
type
Fault in external device 2. Check the external device.
Check setting of parameter 31.03
External event 2 source.
A983 External warning 3
(Editable message text)
Programmable warning:
31.05 External event 3
source
31.06 External event 3
type
Fault in external device 3. Check the external device.
Check setting of parameter 31.05
External event 3 source.
A984 External warning 4
(Editable message text)
Programmable warning:
31.07 External event 4
source
31.08 External event 4
type
Fault in external device 4. Check the external device.
Check setting of parameter 31.07
External event 4 source.
A985 External warning 5
(Editable message text)
Programmable warning:
31.09 External event 5
source
31.10 External event 5
type
Fault in external device 5. Check the external device.
Check setting of parameter 31.09
External event 5 source.
AF80 INU-LSU comm loss
Programmable warning:
60.79 INU-LSU comm loss
function
DDCS (fiber optic)
communication between
converters (for example, the
inverter unit and the supply
unit) is lost.
Note that the inverter unit will
continue operating based on
the status information that was
last received from the other
converter.
Check status of other converter
(parameters 06.36 and 06.39).
Check settings of parameter group 60
DDCS communication. Check the
corresponding settings in the control
program of the other converter.
Check cable connections. If necessary,
replace cables.
AF85 Line side unit warning The supply unit (or other
converter) has generated a
warning.
The auxiliary code specifies the original
warning code in the supply unit control
program. See section Auxiliary codes for
line-side converter warnings (page 539).
AF8C Process PID sleep
mode
The drive is entering sleep
mode.
Informative warning. See section Sleep
function for process PID control (page
67), and parameters 40.41…40.48.
AF90 Speed controller
autotuning
The speed controller autotune
routine did not complete
successfully.
Check the auxiliary code (format XXXX
YYYY). “YYYY” indicates the problem
(see actions for each code below).
0000 The drive was stopped before
the autotune routine finished.
Repeat autotune until successful.
Code
(hex)
Warning Cause What to do