Fault tracing 529
001C A nonexisting parameter or
block is used in the program.
Edit the program to correct the parameter
reference, or to use an existing block.
001D Parameter type invalid for
selected pin.
Edit the program to correct the parameter
reference.
001E Output to parameter failed
because the parameter was
write-protected.
Check the parameter reference in the
program.
Check for other sources affecting the
target parameter.
0023 Program file incompatible with
current firmware version.
Adapt the program to current block
library and firmware version.
0024
002A Too many blocks. Edit the program to reduce the number of
blocks.
Other Contact your local ABB representative,
quoting the auxiliary code.
64B0 Memory unit detached The memory unit was
detached when the control unit
was powered.
Switch off the power to the control unit
and reinstall the memory unit.
In case the memory unit was not actually
removed when the fault occurred, check
that the memory unit is properly inserted
into its connector and its mounting screw
is tight. Reboot the control unit (using
parameter 96.08 Control board boot) or
by cycling power. If the problem persists,
contact your local ABB representative.
64B1 Internal SSW fault Internal fault. Reboot the control unit (using parameter
96.08 Control board boot) or by cycling
power. If the problem persists, contact
your local ABB representative.
64B2 User set fault Loading of user parameter set
failed because
set is not compatible with
control program
drive was switched off
during loading.
Ensure that a valid user parameter set
exists. Reload if uncertain.
64E1 Kernel overload Operating system error. Reboot the control unit (using parameter
96.08 Control board boot) or by cycling
power. If the problem persists, contact
your local ABB representative.
64FF Fault reset Informative fault. An active fault has been reset.
6581 Parameter system Parameter load or save failed. Try forcing a save using parameter 96.07
Parameter save manually. Retry.
65A1 FBA A parameter
conflict
The drive does not have a
functionality requested by
PLC, or requested functionality
has not been activated.
Check PLC programming.
Check settings of parameter groups 50
Fieldbus adapter (FBA) and 51 FBA A
settings.
65A2 FBA B parameter
conflict
The drive does not have a
functionality requested by
PLC, or requested functionality
has not been activated.
Check PLC programming.
Check settings of parameter groups 50
Fieldbus adapter (FBA) and 54 FBA B
settings.
Code
(hex)
Fault Cause What to do