DescriptionExample valueNameIndex
Sets the minimum ramp time for the SAR0
ramp monitoring.
500 msSAR0 min ramp time
to zero
SARx.11
This parameter is relevant only if parameter
SSE.13 SSE function is set to Emergency
ramp. Adjust the default value when neces-
sary.
Sets the maximum ramp time for the SAR0
ramp monitoring.
1500 msSAR0 max ramp time
to zero
SARx.12
This parameter is relevant only if parameter
SSE.13 SSE function is set to Emergency
ramp. Adjust the default value when neces-
sary.
Parameters for the SLS function
There are four separate SLS functions (SLS1…4) in the FSO module. The SLS functions
are identical and the configuration is done similarly, only the parameter numbers differ. The
SLS1 function is shown as an example. ABB has activated the SLS1 function at the factory.
For more information, see FSO module user’s manual.
DescriptionExample valueNameIndex
Activates or deactivates the SLS1 function
and shows the version of the SLS1 function.
Version 1SLS1 activity and
version
200.21
Disabled: Deactivates the SLS1 function.
Version 1: Activates the SLS1 function.
Sets the SLS1 negative speed limit for the
drive.
-200 rpmSLS1 limit negative200.22
Adjust the default value to meet the motor
in use.
Note: The difference between the SLS limit
and the corresponding SLS trip limit
(SLSx.13 SLS1 trip limit negative) must be
at least 0.1 rpm.
Sets the SLS1 positive speed limit for the
drive.
200 rpmSLS1 limit positive200.23
Adjust the default value to meet the motor
in use.
Note: The difference between the SLS limit
and the corresponding SLS trip limit
(SLSx.14 SLS1 trip limit positive) must be
at least 0.1 rpm.
Sets the acknowledgement method used in
the SLS1…4 functions.
AutomaticSLS acknowledge-
ment
SLSx.02
Automatic: The FSO module generates the
SLS acknowledgment signal automatically
after the SLS request is removed and the
SLS limit is achieved. The user does not
have to press a reset button (see parameter
FSOGEN.42 Acknowledgement button in-
put).
Parameter settings 43