you must document all validation tests
you must sign and store the validation test report for further reference.
Validation test reports
You must store the signed validation test reports in the logbook of the machine. The report
must include, as required by the referred standards:
a description of the safety application (including a figure)
a description and revisions of safety components that are used in the safety application
a list of all safety functions that are used in the safety application
a list of all safety-related parameters and their values
documentation of start-up activities, references to failure reports and resolution of failures
the test results for each safety function, checksums, date of the tests, and confirmation
by the test personnel.
You must store any new validation test reports done due to changes or maintenance in the
logbook of the machine.
Start-up and validation test
You must use the Drive composer PC tool to do the start-up and validation test. Repeat the
test in both operation directions of the motor.
Note: The SLS validation test procedure described in this chapter does not test the trip
limits, because the SLS function limits the motor reference speed to the SLS limit. ABB has
validated the functionality of trip limits in the verification tests.
Note: If you use SMS function, version 2: Do the validation test as described in the FSO
module user’s manual.
Action
WARNING!
Obey the safety instructions. If you ignore them, injury or death, or damage to the
equipment can occur.
Initial status
Safety encoder interface:
If you use a safety encoder in the safety application, validate the safety encoder interface as described
in FSO-21 safety functions module user’s manual (3AXD50000015614 [English]), chapter Verification
and validation.
Make sure that the drive is ready for use, that is, you have done the tasks of the drive start-up procedure.
See the hardware manual.
Before you do the motor ID run, you must deactivate the SLS and SMS functions:
SLS function: Make sure that the SLS request is not active (for example, from a switch).
SMS function: Set parameter 200.71 SMS activity and version to value Disabled.
After the motor ID run, activate the SLS and SMS functions.
54 Start-up and validation test