90 Electrical installation
Drive-to-drive link
The drive-to-drive link is a daisy-chained RS-485 transmission line that allows basic
master/follower communication with one master drive and multiple followers. Enable
bus termination on the drives at the ends of the drive-to-drive link. On intermediate
drives, disable bus termination.
The settings for each type of control unit are:
Cables for drive-to-drive connection
Use shielded twisted-pair cable (~100 ohm, for example, PROFIBUS-compatible
cable) for the wiring. For best immunity, high quality cable is recommended.
Keep the cable as short as possible. The maximum length of the link is 50 meters
(164 ft).
Avoid unnecessary loops and running the cable near power cables (such as
motor cables).
Ground the cable shields as described in section Connecting the control cables –
all frame sizes on page 96.
Example wiring diagram of drive-to-drive link
Control unit type Switch/jumper
designation
Settings
ZCU-14
(frame sizes R1…R4)
J3 Termination enabled
Termination disabled
1
2
3
4
B
A
BGND
Shield
XD2D
Termination OFF
1
2
3
4
B
A
BGND
Shield
XD2D
1
2
3
4
B
A
BGND
Shield
XD2D
Termination ONTermination ON