- / uint16ACS800-compatible fault word 1.
The bit assignments of this word correspond to FAULT
WORD 1 in the ACS800. Parameter 4.120 Fault/Warning
word compatibility determines whether the bit
assignments are according to the ACS800 Standard or
ACS800 System control program.
Each bit can indicate several ACS880 events as listed
below.
This parameter is read-only.
ACS880
events indic-
ated by this
bit
(see Fault tra-
cing(page 547).
ACS880 fault nameBit
(4.120 =
ACS800 Sys-
tem ctrl pro-
gram)
(4.120 =
ACS800
Standard ctrl
program)
2340SHORT CIRCSHORT CIRC0
2310OVERCUR-
RENT
OVERCUR-
RENT
1
3210DC OVERVOLTDC OVERVOLT2
2381, 4210,
4290, 42F1,
4310, 4380
ACS800 TEMPACS800 TEMP3
2330, 2392,
3181
EARTH FAULTEARTH FAULT4
4981, 4991,
4992, 4993
MOTOR TEMP
M
THERMISTOR5
4982MOTOR TEMPMOTOR TEMP6
6481, 6487,
64A1, 64A2,
64A3, 64B1,
64E1, 6881,
6882, 6883,
6885
SYS-
TEM_FAULT
SYS-
TEM_FAULT
7
-UNDERLOADUNDERLOAD8
7310OVERFREQOVERFREQ9
9081MPROT
SWITCH
Reserved10
7582CH2 COMM
LOSS
Reserved11
2340 (XXYY
YY01)
SC (INU1)Reserved12
2340 (XXYY
YY02)
SC (INU2)Reserved13
2340 (XXYY
YY03)
SC (INU3)Reserved14
2340 (XXYY
YY04)
SC (INU4)Reserved15
Fault word 14.21
144 Parameters