Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
- / uint16ACS800-compatible fault word 2.
The bit assignments of this word correspond to FAULT
WORD 2 in the ACS800. Parameter 4.120 Fault/Warning
word compatibility determines whether the bit
assignments are according to the ACS800 Standard or
ACS800 System control program.
Each bit can indicate several ACS880 events as listed
below.
This parameter is read-only.
ACS880
events indic-
ated by this
bit
(see Fault tra-
cing(page 547).
ACS880 fault name
Bit
(4.120 =
ACS800 Sys-
tem ctrl pro-
gram)
(4.120 =
ACS800
Standard ctrl
program)
3130SUPPLY
PHASE
SUPPLY
PHASE
0
-NO MOTOR
DATA
NO MOT DATA1
3220DC UNDER-
VOLT
DC UNDER-
VOLT
2
4000CABLE TEMPReserved3
AFEBRUN DISABLERUN ENABLE4
7301, 7380,
7381, 73A0,
73A1
ENCODER ERRENCODER ERR5
7080, 7082IO COMM ERRI/O COMM6
-CTRL B TEMPCTRL B TEMP7
9082SELECTABLEEXTERNAL
FLT
8
-OVER SW-
FREQ
OVER SW-
FREQ
9
80A0AI<MIN FUNCAI < MIN FUNC10
5681, 5682,
5690, 5691,
5692, 5693,
5694, 5695
PPCC LINKPPCC LINK11
6681, 7510,
7520, 7581
COMM MOD-
ULE
COMM MOD-
ULE
12
7081PANEL LOSSPANEL LOSS13
7121MOTOR STALLMOTOR STALL14
3381MOTOR
PHASE
MOTOR
PHASE
15
Fault word 24.22
Parameters 145

Table of Contents