Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
0 % / real32Displays the age of the auxiliary cooling fan as a
percentage of its estimated lifetime. The estimate is
based on the duty, operating conditions and other
operating parameters of the fan. When the counter
reaches 100%, a warning (A8C0 Fan service counter) is
generated.
Can be reset from the control panel by keeping Reset
depressed for over 3 seconds.
Aux. fan service
counter
5.42
1 = 1 % / 1 = 1 %Auxiliary cooling fan age.0...150 %
- / real32
(Only visible when IGBT supply unit control activated
by
95.20
)
Estimated supply unit temperature in percent of fault
limit.
0.0 % = 0 °C (32 °F)
94 % approx. = Warning limit
100.0 % = Fault limit
Line converter
temperature
5.111
1 = 1 % / 10 = 1 %Supply unit temperature in percent.-40.0 ... 160.0 %
- / uint32
(Only visible when IGBT supply unit control activated
by
95.20
)
Counts the closures of the main circuit breaker of the
supply unit.
MCB closing counter5.121
1 = 1 / 1 = 1Count of closures of main circuit breaker.0...4294967295
Parameters 151