Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
11Digital input/output DIO1 (11.2 DIO delayed status, bit
0).
DIO2
See Terms and abbreviations (page 130).Other [bit]
Not selected / uint32If enabled by parameter 20.25 Jogging enable, selects
the source for the activation of jogging function 2.
(Jogging function 2 can also be activated through
fieldbus regardless of parameter 20.25.)
1 = Jogging 2 active.
For the selections, see parameter 20.26 Jogging 1 start
source.
Note: If both jogging 1 and 2 are activated, the one that
was activated first has priority.
Jogging 2 start
source
20.27
Edge / uint16Defines whether the start signal for local control (for
example, control panel or PC tool) is edge-triggered or
level-triggered.
Local start trigger
type
20.29
0The start signal is edge-triggered.Edge
1The start signal is level-triggered.Level
- / uint16Selects enable signal (eg. run enable, start enable)
warnings to be suppressed. This parameter can be used
to prevent these warnings from flooding the event log.
Whenever a bit of this parameter is set to 1, the
corresponding warning is suppressed, ie. no warning
is generated even if the signal is switched off.
The bits of this binary number correspond to the
following warnings:
Enable signals
warning function
20.30
AFEA Enable start signal missingEnable Startb0
AFEB Run enable missingRun enable 1b1
Reservedb2…15
1 = 10000h…FFFFh
Parameters 251