Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
- / uint16
(Only visible when IGBT supply unit control activated
by
95.20
)
Displays limit word 4 of the supply unit.
This parameter is read-only.
LSU limit word 430.104
1 = DC reference is being limited by supply control
program parameters
Udc ref maxb0
1 = DC reference is being limited by supply control
program parameters
Udc ref minb1
1 = Current is being limited by supply control program
parameters
User I maxb2
1 = Current is being limited based on temperatureTemp I maxb3
Reservedb4…15
1 = 10000h…FFFFh
-130.0 % / real32
(Only visible when IGBT supply unit control activated
by
95.20
)
Defines a minimum power limit for the supply unit.
Negative values refer to regenerating, ie. feeding power
into the supply network.
LSU minimum power
limit
30.148
1 = 1 % / 10 = 1 %Minimum power limit for supply unit.-200.0 ... 0.0 %
130.0 % / real32
(Only visible when IGBT supply unit control activated
by
95.20
)
Defines a maximum power limit for the supply unit.
LSU maximum
power limit
30.149
1 = 1 % / 10 = 1 %Maximum power limit for supply unit.0.0 ... 200.0 %