Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
1 = Channel CH12 is routed to a local power unitb11
Reservedb12…15
1 = 10000h…FFFFh
- / uint16Specifies hardware-related options that require
differentiated parameter defaults. Activating a bit in
this parameter makes the necessary changes in other
parameters. For example, activating an emergency stop
option reserves a digital input. In many cases, the
differentiated parameters will also be write-protected.
This parameter, as well as the changes in other
parameters implemented by it, are not affected by a
parameter restore.
WARNING! After switching any bits in this word,
recheck the values of the affected parameters.
Note: This parameter cannot be changed while the
drive is running.
*See section Control of a supply unit (LSU) (page 76).
HW options word 195.20
0 = 50 Hz; 1 = 60 Hz. Affects 11.45, 11.59, 12.20, 13.18,
30.11, 30.12, 31.26, 31.27, 46.1, 46.2.
Supply frequency 60
Hz
b0
1 = Emergency stop, Category 0, without FSO module.
Affects 21.4, 21.5, 23.11.
Emergency stop Cat
0
b1
1 = Emergency stop, Category 1, without FSO module.
Affects 10.24, 21.4, 21.5, 23.11.
Emergency stop Cat
1
b2
1 = Control of cabinet cooling fan (used only with
specific ACS880-07 hardware). Affects 10.27, 10.28,
10.29.
RO2 for -07 cabinet
cooling fan
b3
1 = Control unit powered externally. Affects 95.4.
(Only
visible with a ZCU control unit)
Externally powered
control unit
b4
1 = DC switch monitoring active. Affects 20.12, 31.3,
95.8.
(Only visible with a ZCU control unit)
DC supply switchb5
1 = Motor fan control active. Affects 10.24, 35.100,
35.103, 35.104.
DOL motor switchb6
1 = xSFC charging controller used. Affects 95.9.
(Only
visible with a BCU control unit)
xSFC-01 fuse switch
controller
b7
1 = Service switch or PTC/Pt100 relay connected.
Affects 31.1, 31.2.
Service switch or
PTC/Pt100 relay
b8
1 = Output contactor present. Affects 10.24, 20.12.Output contactorb9
1 = Status (eg. thermal) switches connected to DIIL
input. Affects 20.11, 20.12.
Brake resistor, sine
filter, IP54 fan
b10
*1 = Diode supply unit control by inverter unit active.
Makes several parameters visible in groups 6, 60, 61,
62 and 94.
(Only visible with a BCU control unit)
INU-DSU
communication
b11
Reservedb12
Parameters 513