Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
4Load user parameter set 3.Load set 3
5Load user parameter set 4.Load set 4
18Save user parameter set 1.Save to set 1
19Save user parameter set 2.Save to set 2
20Save user parameter set 3.Save to set 3
21Save user parameter set 4.Save to set 4
Not selected / uint32When parameter 96.11 is set to User set I/O mode,
selects the user parameter set together with parameter
96.13 as follows:
User parameter
set selected
Status of
source defined
by 96.13
Status of
source defined
by 96.12
Set 100
Set 201
Set 310
Set 411
User set I/O mode
in1
96.12
00Not selected
11Selected
2Digital input DI1 (10.2 DI delayed status, bit 0).DI1
3Digital input DI2 (10.2 DI delayed status, bit 1).DI2
4Digital input DI3 (10.2 DI delayed status, bit 2).DI3
5Digital input DI4 (10.2 DI delayed status, bit 3).DI4
6Digital input DI5 (10.2 DI delayed status, bit 4).DI5
7Digital input DI6 (10.2 DI delayed status, bit 5).DI6
10Digital input/output DIO1 (11.2 DIO delayed status, bit
0).
DIO1
11Digital input/output DIO2 (11.2 DIO delayed status, bit
1).
DIO2
See Terms and abbreviations (page 130).Other [bit]
Not selected / uint32See parameter 96.12 User set I/O mode in1.User set I/O mode
in2
96.13
- / uint16Selects the unit of parameters indicating power,
temperature and torque.
Unit selection96.16
0 = kW
1 = hp
Power unitb0
Reservedb1
0 = C (°C)
1 = F (°F)
Temperature unitb2
Reservedb3
520 Parameters