CH1
CH2
CH3 CH4 CH1
CH2 CH3 CH4
Module 1
Module 2 Module 3 Module 4
BCU 1
95.16
=
On
95.17
= 1100b
BCU 2
95.14
= 000Fh (1111b)
95.16
=
Off
Note:
The local modules must be connected to successive channels starting from
CH1. The immediately following channels are connected to the other BCU and
routed to the local modules. There must be at least as many local modules as
there are routed channels.
In PLC control, any switch-overs must be done in stopped state, and so that
at least one BCU is in router mode at any given time.
Additional rules or restrictions may apply when using the router mode with
other control programs. See the appropriate firmware manual.
Settings and diagnostics
Parameters: 95.16 Router mode (page 597) and 95.17 Router channel config (page 597).
Program features 147