ABB ACS880 - Default Control Connections for the Factory Macro; Default Parameter Settings for the Factory Macro; Factory Macro

ABB ACS880
764 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Factory macro
The Factory macro is suited to relatively straightforward speed control applications
such as conveyors, pumps and fans, and test benches.
The drive is speed-controlled with the reference signal connected to analog input
AI1. The start/stop commands are given through digital input DI1; running direction
is determined by DI2. This macro uses control location EXT1.
Faults are reset through digital input DI3.
DI4 switches between acceleration/deceleration time sets 1 and 2. The acceleration
and deceleration times, as well as ramp shapes, are defined by parameters
23.1223.19.
DI5 activates constant speed 1.
Default parameter settings for the Factory macro
The default parameter settings for the Factory macro are listed in chapter
Parameter listing (page 174).
Default control connections for the Factory macro
DescriptionTermConnection
XPOW External power input
24 V DC, 2 A
+24VI
1
2
+24VI
GND
GND
XAI Reference voltage and analog inputs
10 V DC,
R
L
1…10 kohm+VREF
+VREF
-VREF
AGND
AI1+
AI1-
AI2+
AI2-
1
2
3
4
5
6
7
-10 V DC,
R
L
1…10 kohm-VREF
GroundAGND
Speed reference
0(2)…10 V,
R
in
> 200 kohm
AI1+
AI1-
By default not in use.
0(4)…20 mA,
R
in
= 100 ohm
AI2+
AI2-
XAO Analog outputs
Motor speed rpmAO1
AO1
AGND
AO2
AGND
1
2
3
4
0…20 mA,
R
L
< 500 ohm
AGND
Motor current
0…20 mA,
R
L
< 500 ohm
AO2
AGND
150 Application macros