Loading...
DescriptionTermConnection
Digital interlock. By default, not in use.DIIL
DIIL1
+24VD
DICOM
+24VD
DIOGND
2
3
4
5
+24 V DC 200 mA+24VD
Digital input groundDICOM
+24 V DC 200 mA+24VD
Digital input/output groundDIOGND
XDIO Digital input/outputs
Output: Ready runDIO1
1 DIO1
2
DIO2
Output: RunningDIO2
XDI Digital inputs
Stop (0) / Start (1) Speed controlDI1
1
DI1
DI2
DI3
DI4
DI5
DI6
2
3
4
5
6
+24VD
By default, not in use.DI2
Speed control (0) / Process control (1)DI3
Constant speed 1 (1 = On)DI4
Run enable (1 = On)DI5
Stop (0) / Start (1) Process controlDI6
Safe torque off circuits must be closed for the drive
to start. See
Hardware manual
of drive.
XSTO
Safety options connectionX12
Control panel connectionX13
Memory unit connectionX205
1)
For sensor connection examples, see page 159.