Selection of constant speeds
By default, constant speeds 1…7 are selected using digital inputs DI4…DI6 as
follows:
Constant speed activeDI6DI5DI4
None (External speed reference used)000
Constant speed 1001
Constant speed 2010
Constant speed 3011
Constant speed 4100
Constant speed 5101
Constant speed 6110
Constant speed 7111
■
Default parameter settings for the Sequential control macro
Below is a listing of default parameter values that differ from those listed for the
Factory macro in Parameter listing (page 174).
Sequential control macro defaultParameter
DIIL20.12 Run enable 1 source
Ramp21.3 Stop mode
01b (Bit 0 = Packed)22.21 Constant speed function
DI422.22 Constant speed sel1
DI522.23 Constant speed sel2
DI622.24 Constant speed sel3
600.00 rpm22.27 Constant speed 2
900.00 rpm22.28 Constant speed 3
1200.00 rpm22.29 Constant speed 4
1500.00 rpm22.30 Constant speed 5
2400.00 rpm22.31 Constant speed 6
3000.00 rpm22.32 Constant speed 7
DI323.11 Ramp set selection
0.12 s25.6 Acc comp derivation time
Not selected31.11 Fault reset selection
164 Application macros