Selection of constant speeds
By default, constant speeds 1…7 are selected using digital inputs DI4…DI6 as
follows:
Constant speed activeDI6DI5DI4
None (External speed reference used)000
Constant speed 1001
Constant speed 2010
Constant speed 3011
Constant speed 4100
Constant speed 5101
Constant speed 6110
Constant speed 7111
Default parameter settings for the Sequential control macro
Below is a listing of default parameter values that differ from those listed for the
Factory macro in Parameter listing (page 174).
Sequential control macro defaultParameter
DIIL20.12 Run enable 1 source
Ramp21.3 Stop mode
01b (Bit 0 = Packed)22.21 Constant speed function
DI422.22 Constant speed sel1
DI522.23 Constant speed sel2
DI622.24 Constant speed sel3
600.00 rpm22.27 Constant speed 2
900.00 rpm22.28 Constant speed 3
1200.00 rpm22.29 Constant speed 4
1500.00 rpm22.30 Constant speed 5
2400.00 rpm22.31 Constant speed 6
3000.00 rpm22.32 Constant speed 7
DI323.11 Ramp set selection
0.12 s25.6 Acc comp derivation time
Not selected31.11 Fault reset selection