Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
- / uint16Start inhibit status word. This word specifies the source
of the inhibiting condition that is preventing the drive
from starting.
After the condition is removed, the start command
must be cycled. See bit-specific notes.
See also parameter 6.25 Drive inhibit status word 2,
and 6.16 Drive status word 1, bit 1.
This parameter is read-only.
Note:
If bit 1 of 6.16 Drive status word 1 is still set after
the removal of the inhibiting condition, and edge
triggering is selected for the active external
control location, a fresh rising-edge start signal
is required. See parameters 20.2, 20.7 and 20.19.
If bit 1 of 6.16 Drive status word 1 is still set after
the removal of the inhibiting condition, a fresh
rising-edge start signal is required.
Informative bit. The inhibiting condition need not
be removed by the user.
Start inhibit status
word
6.18
1 = DC voltage is missing or drive has not been
parametrized correctly. Check the parameters in groups
95 and 99.
Not ready runb0
1 = Control location has changedCtrl location
changed
b1
1 = Control program is keeping itself in inhibited stateSSW inhibitb2
1 = A fault is activeFaultb3
1 = Start enable signal missingLost start enableb4
1 = Run enable signal missingLost run enableb5
1 = Operation prevented by FSO-xx safety functions
module
FSO inhibitb6
1 = Safe torque off activeSTOb7
1 = Current calibration routine has finishedCurrent calibration
ended
b8
1 = Motor identification run has finishedID run endedb9
1 = Autophasing routine has finishedAuto phase endedb10
1 = Emergency stop signal (mode Off1)Off1b11
1 = Emergency stop signal (mode Off2)Em Off2b12
1 = Emergency stop signal (mode Off3)Em Off3b13
1 = The autoreset function is inhibiting operationAuto reset inhibitb14
1 = The jogging enable signal is inhibiting operationJogging activeb15
1 = 10000h…FFFFh
- / uint16Speed control status word.
This parameter is read-only.
Speed control status
word