Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
1 = Constant speed or frequency 3 selectedConstant speed 3b2
1 = Constant speed or frequency 4 selectedConstant speed 4b3
1 = Constant speed or frequency 5 selectedConstant speed 5b4
1 = Constant speed or frequency 6 selectedConstant speed 6b5
1 = Constant speed or frequency 7 selectedConstant speed 7b6
Reservedb7…15
1 = 10000h…FFFFh
- / uint16Drive status word 3.
This parameter is read-only.
Drive status word 36.21
1 = DC hold is active (see par. 21.8)DC hold activeb0
1 = Post-magnetizing is active (see par. 21.8)Post-magnetizing
active
b1
1 = Motor pre-heating is active (see par. 21.14)Motor pre-heating
active
b2
ReservedSmooth start activeb3
1 = Rotor position has been determined (autophasing
not needed). See section Autophasing (page 102).
Rotor position
known
b4
Brake chopper active. See section Brake
chopper (page 122).
Brake chopper
active
b5
Motor temperature
estimation active
b6
Reservedb7…15
1 = 10000h…FFFFh
- / uint16Drive inhibit status word 2. This word specifies the
source of the inhibiting condition that is preventing
the drive from starting. After the condition is removed,
the start command must be cycled. See bit-specific
notes.
See also parameter 6.18 Start inhibit status word, and
6.16 Drive status word 1, bit 1.
This parameter is read-only.
Note:
• If bit 1 of 6.16 Drive status word 1 is still set after
the removal of the inhibiting condition, and edge
triggering is selected for the active external
control location, a fresh rising-edge start signal
is required. See parameters 20.2, 20.7 and 20.19.
• If bit 1 of 6.16 Drive status word 1 is still set after
the removal of the inhibiting condition, a fresh
rising-edge start signal is required.
Drive inhibit status
word 2
6.25
1 = A follower is preventing the master from starting.Follower driveb0
1 = The application program is preventing the drive
from starting.
Applicationb1
196 Parameters