Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
0.0 s / uint32Defines the activation delay for digital input DI5.
*DI status
**Delayed
DI status
t
On
t
Off
t
On
t
Off
Time
1
0
1
0
t
On
= 10.13 DI5 ON delay
t
Off
= 10.14 DI5 OFF delay
*Electrical status of digital input. Indicated by 10.1 DI
status.
**Indicated by 10.2 DI delayed status.
DI5 ON delay10.13
10 = 1 s / 10 = 1 sActivation delay for DI5.0.0 ... 3000.0 s
0.0 s / uint32Defines the deactivation delay for digital input DI5. See
parameter 10.13 DI5 ON delay.
DI5 OFF delay10.14
10 = 1 s / 10 = 1 sDeactivation delay for DI5.0.0 ... 3000.0 s
0.0 s / uint32Defines the activation delay for digital input DI6.
*DI status
**Delayed
DI status
t
On
t
Off
t
On
t
Off
Time
1
0
1
0
t
On
= 10.15 DI6 ON delay
t
Off
= 10.16 DI6 OFF delay
*Electrical status of digital input. Indicated by 10.1 DI
status.
**Indicated by 10.2 DI delayed status.
DI6 ON delay10.15
10 = 1 s / 10 = 1 sActivation delay for DI6.0.0 ... 3000.0 s
0.0 s / uint32Defines the deactivation delay for digital input DI6. See
parameter 10.15 DI6 ON delay.
DI6 OFF delay10.16
10 = 1 s / 10 = 1 sDeactivation delay for DI6.0.0 ... 3000.0 s
- / uint16Status of relay outputs RO8…RO1. Example: 00000001b
= RO1 is energized, RO2…RO8 are de-energized.
RO status10.21
Ready run; 10.01 b3
(-1) (95.20 b2); 35.105
b1 (95.20 b6); 06.16
b6 (95.20 b9) / uint32
Selects a drive signal to be connected to relay output
RO1.
RO1 source10.24
0Output is not energized.Not energized
1Output is energized.Energized
2Bit 1 of 6.11 Main status word (page 192).Ready run
4Bit 0 of 6.16 Drive status word 1 (page 192).Enabled
214 Parameters