EasyManua.ls Logo

ABB ACS880 - Page 221

ABB ACS880
764 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
0 Hz / real32Defines the minimum for the frequency actually arriving
at frequency input 1 (DIO1 when it is used as a
frequency input).
The incoming frequency signal (11.38 Freq in 1 actual
value) is scaled into an internal signal (11.39 Freq in 1
scaled) by parameters 11.4211.45 as follows:
11.39
f
in
(
11.38
)
11.42 11.43
11.45
11.44
Freq in 1 min11.42
1 = 1 Hz / 1 = 1 HzMinimum frequency of frequency input 1 (DIO1).0...16000 Hz
16000 Hz / real32Defines the maximum for the frequency actually arriving
at frequency input 1 (DIO1 when it is used as a
frequency input).
See parameter 11.42 Freq in 1 min.
Freq in 1 max11.43
1 = 1 Hz / 1 = 1 HzMaximum frequency for frequency input 1 (DIO1).0...16000 Hz
0.000 / real32Defines the value that is required to correspond
internally to the minimum input frequency defined by
parameter 11.42 Freq in 1 min. See diagram at
parameter 11.42 Freq in 1 min.
Freq in 1 at scaled
min
11.44
1 = 1 / 1000 = 1Value corresponding to minimum of frequency input
1.
-32768.000 ...
32767.000
1500.000; 1800.000
(95.20 b0) / real32
Defines the value that is required to correspond
internally to the maximum input frequency defined by
parameter 11.43 Freq in 1 max. See diagram at
parameter 11.42 Freq in 1 min.
Freq in 1 at scaled
max
11.45
1 = 1 / 1000 = 1Value corresponding to maximum of frequency input
1.
-32768.000 ...
32767.000
- / real32Displays the value of frequency output 1 after scaling.
See parameter 11.58 Freq out 1 src min.
This parameter is read-only.
Freq out 1 actual
value
11.54
1 = 1 Hz / 1 = 1 HzValue of frequency output 1.0...16000 Hz
Motor speed used /
uint32
Selects a signal to be connected to frequency output
1.
Freq out 1 source11.55
0NoneZero
11.1 Motor speed used (page 174).Motor speed used
31.6 Output frequency (page 174).Output frequency
41.7 Motor current (page 174).Motor current
Parameters 221

Table of Contents

Other manuals for ABB ACS880

Related product manuals