Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
1500.000; 1800.000
(95.20 b0) / real32
Defines the real value of the signal (selected by
parameter 11.55 Freq out 1 source and shown by
parameter 11.54 Freq out 1 actual value) that
corresponds to the maximum value of frequency output
1 (defined by parameter 11.61 Freq out 1 at src max).
See parameter 11.58 Freq out 1 src min.
Freq out 1 src max11.59
1 = 1 / 1000 = 1Real signal value corresponding to maximum value of
frequency output 1.
-32768.000 ...
32767.000
0 Hz / real32Defines the minimum value of frequency output 1. See
diagrams at parameter 11.58 Freq out 1 src min.
Freq out 1 at src min11.60
1 = 1 Hz / 1 = 1 HzMinimum value of frequency output 1.0...16000 Hz
16000 Hz / real32Defines the maximum value of frequency output 1. See
diagrams at parameter 11.58 Freq out 1 src min.
Freq out 1 at src max11.61
1 = 1 Hz / 1 = 1 HzMaximum value of frequency output 1.0...16000 Hz
10.0 ms / uint32Defines a filtering time for parameter 11.1 DIO status
and 11.2 DIO delayed status. The filtering time will only
affect the DIOs that are in input mode.
DIO filter time11.81
10 = 1 ms / 10 = 1 msFiltering time for 11.1.0.3 ... 100.0 ms