Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
0.0 / real32Defines the real minimum value of the signal (selected
by parameter 13.12 AO1 source) that corresponds to
the minimum required AO1 output value (defined by
parameter 13.19 AO1 out at AO1 src min).
I
AO1
(mA)
Signal (real)
selected by
13.12
13.20
13.19
13.17
13.18
Programming 13.17 as the maximum value and 13.18 as
the minimum value inverts the output.
I
AO1
(mA)
Signal (real)
selected by
13.12
13.20
13.19
13.18
13.17
AO1 source min13.17
1 = 1 / 10 = 1Real signal value corresponding to minimum AO1
output value.
-32768.0 ... 32767.0
1500.000; 1800.000
(95.20 b0) / real32
Defines the real maximum value of the signal (selected
by parameter 13.12 AO1 source) that corresponds to
the maximum required AO1 output value (defined by
parameter 13.20 AO1 out at AO1 src max). See
parameter 13.17 AO1 source min.
AO1 source max13.18
1 = 1 / 10 = 1Real signal value corresponding to maximum AO1
output value.
-32768.0 ... 32767.0