Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
0.000 mA / real32Defines the minimum output value for analog output
AO2.
See also drawing at parameter 13.27 AO2 source min.
AO2 out at AO2 src
min
13.29
1000 = 1 mA / 1000 =
1 mA
Minimum AO2 output value.0.000 ... 22.000 mA
20.000 mA / real32Defines the maximum output value for analog output
AO2.
See also drawing at parameter 13.27 AO2 source min.
AO2 out at AO2 src
max
13.30
1000 = 1 mA / 1000 =
1 mA
Maximum AO2 output value.0.000 ... 22.000 mA
0.00 / real32Storage parameter for controlling analog output AO1
eg. through fieldbus.
In 13.12 AO1 source, select AO1 data storage. Then set
this parameter as the target of the incoming value data.
With the embedded fieldbus interface, simply set the
target selection parameter of that particular data
(58.101…58.124) to AO1 data storage.
AO1 data storage13.91
100 = 1 / 100 = 1Storage parameter for AO1.-327.68 ... 327.67
0.00 / real32Storage parameter for controlling analog output AO2
eg. through fieldbus.
In 13.22 AO2 source, select AO2 data storage. Then set
this parameter as the target of the incoming value data.
With the embedded fieldbus interface, simply set the
target selection parameter of that particular data
(58.101…58.124) to AO2 data storage.
AO2 data storage13.92
100 = 1 / 100 = 1Storage parameter for AO2.-327.68 ... 327.67
Parameters 235