Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
0Tuning action completed or no action has been
requested.
The parameter automatically reverts to this value after
any tuning action.
No action
1The measured value of AI1 is set as the minimum value
of AI1 into parameter 14.33 AI1 min.
AI1 min tune
2The measured value of AI1 is set as the maximum value
of AI1 into parameter 14.34 AI1 max.
AI1 max tune
3The measured value of AI2 is set as the minimum value
of AI2 into parameter 14.48 AI2 min.
AI2 min tune
4The measured value of AI2 is set as the maximum value
of AI2 into parameter 14.49 AI2 max.
AI2 max tune
5The measured value of AI3 is set as the minimum value
of AI3 into parameter 14.63 AI3 min.
AI3 min tune
6The measured value of AI3 is set as the maximum value
of AI3 into parameter 14.64 AI3 max.
AI3 max tune
Not energized /
uint32
(Visible when 14.1 Module 1 type = FIO-01)
Selects a drive signal to be connected to digital
input/output DIO3 when parameter 14.19 DIO3 function
is set to Output.
For the available selections, see parameter 14.11 DIO1
output source.
DIO3 output source14.21
- / uint16(Visible when 14.1 Module 1 type = FAIO-01)
The true readings of the analog inputs can be
overridden for eg. testing purposes. A forced value
parameter is provided for each analog input, and its
value is applied whenever the corresponding bit in this
parameter is 1.
AI force selection14.22
1 = Force mode: Force AI1 to value of parameter 14.28
AI1 force data.
AI1b0
1 = Force mode: Force AI2 to value of parameter 14.43
AI2 force data.
AI2b1
Reservedb2…15
1 = 10000h…FFFFh
0.00 s / real32(Visible when 14.1 Module 1 type = FDIO-01)
Defines the activation delay for digital input DI3. See
parameter 14.12 DI1 ON delay.
DI3 ON delay14.22
10 = 1 s / 100 = 1 sActivation delay for DI3.0.00 ... 3000.00 s
- / uint16(Visible when 14.1 Module 1 type = FIO-11)
The true readings of the analog inputs can be
overridden for eg. testing purposes. A forced value
parameter is provided for each analog input, and its
value is applied whenever the corresponding bit in this
parameter is 1.
AI force selection14.22
1 = Force mode: Force AI1 to value of parameter 14.28
AI1 force data.
AI1b0
Parameters 245