Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
10 = 1 s / 100 = 1 sActivation delay for DIO4.0.00 ... 3000.00 s
- / real32(Visible when 14.1 Module 1 type = FAIO-01)
Forced value that can be used instead of the true
reading of the input. See parameter 14.22 AI force
selection.
AI1 force data14.28
1000 = 1 mA or V /
1000 = 1 mA or V
Forced value of analog input AI1.-22.000 ... 22.000 mA
or V
0.00 s / real32(Visible when 14.1 Module 1 type = FIO-01)
Defines the deactivation delay for digital input/output
DIO4. See parameter 14.12 DIO1 ON delay.
DIO4 OFF delay14.28
10 = 1 s / 100 = 1 sDeactivation delay for DIO4.0.00 ... 3000.00 s
mA / uint16(Visible when 14.1 Module 1 type = FAIO-01)
Shows the position of the hardware current/voltage
selector on the I/O extension module.
Note: The setting of the current/voltage selector must
match the unit selection made in parameter 14.30 AI1
unit selection. I/O module reboot either by cycling the
power or through parameter 96.8 Control board boot
is required to validate any changes in the hardware
settings.
AI1 HW switch
position
14.29
10Milliamperes.mA
2Volts.V
mA / uint16(Visible when 14.1 Module 1 type = FAIO-01)
Selects the unit for readings and settings related to
analog input AI1.
Note: This setting must match the corresponding
hardware setting on the I/O extension module (see the
manual of the I/O extension module). The hardware
setting is shown by parameter 14.29 AI1 HW switch
position. I/O module reboot either by cycling the power
or through parameter 96.8 Control board boot is
required to validate any changes in the hardware
settings.
AI1 unit selection14.30
10Milliamperes.mA
2Volts.V
- / uint16(Visible when 14.1 Module 1 type = FDIO-01)
Status of relay outputs on the I/O extension module.
Example: 0001b = RO1 is energized, RO2 is
de-energized.
RO status14.31
1 ms / uint16(Visible when 14.1 Module 1 type = FAIO-01)
Selects a hardware filtering time for AI1.
See also parameter 14.32 AI1 filter time.
AI1 filter gain14.31
0No filtering.No filtering
1125 microseconds.125 us
2250 microseconds.250 us
3500 microseconds.500 us