Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
0.00 s / real32(Visible when 14.1 Module 1 type = FDIO-01)
Defines the deactivation delay for relay output RO2.
See parameter 14.35 RO1 ON delay.
RO2 OFF delay14.39
10 = 1 s / 100 = 1 sDeactivation delay for RO2.0.00 ... 3000.00 s
0.00 s / real32(Visible when 14.1 Module 1 type = FIO-01)
Defines the deactivation delay for relay output RO2.
See parameter 14.35 RO1 ON delay.
RO2 OFF delay14.39
10 = 1 s / 100 = 1 sDeactivation delay for RO2.0.00 ... 3000.00 s
- / real32(Visible when 14.1 Module 1 type = FAIO-01)
Displays the value of analog input AI2 in mA or V
(depending on whether the input is set to current or
voltage).
This parameter is read-only.
AI2 actual value14.41
1000 = 1 mA or V /
1000 = 1 mA or V
Value of analog input AI2.-22.000 ... 22.000 mA
or V
- / real32(Visible when 14.1 Module 1 type = FAIO-01)
Displays the value of analog input AI2 after scaling. See
parameter 14.50 AI2 scaled at AI2 min.
This parameter is read-only.
AI2 scaled value14.42
1 = 1 mA or V / 1000 =
1 mA or V
Scaled value of analog input AI2.-32768.000 ...
32767.000 mA or V
- / real32(Visible when 14.1 Module 1 type = FAIO-01)
Forced value that can be used instead of the true
reading of the input. See parameter 14.22 AI force
selection.
AI2 force data14.43
1000 = 1 mA or V /
1000 = 1 mA or V
Forced value of analog input AI2.-22.000 ... 22.000 mA
or V
mA / uint16(Visible when 14.1 Module 1 type = FAIO-01)
Shows the position of the hardware current/voltage
selector on the I/O extension module.
Note: The setting of the current/voltage selector must
match the unit selection made in parameter 14.45 AI2
unit selection. I/O module reboot either by cycling the
power or through parameter 96.8 Control board boot
is required to validate any changes in the hardware
settings.
AI2 HW switch
position
14.44
10Milliamperes.mA
2Volts.V
Parameters 251