Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
mA / uint16(Visible when 14.1 Module 1 type = FAIO-01)
Selects the unit for readings and settings related to
analog input AI2.
Note: This setting must match the corresponding
hardware setting on the I/O extension module (see the
manual of the I/O extension module). The hardware
setting is shown by parameter 14.44 AI2 HW switch
position. I/O module reboot either by cycling the power
or through parameter 96.8 Control board boot is
required to validate any changes in the hardware
settings.
AI2 unit selection14.45
10Milliamperes.mA
2Volts.V
1 ms / uint16(Visible when 14.1 Module 1 type = FAIO-01)
Selects a hardware filtering time for AI2.
See also parameter 14.47 AI2 filter time.
AI2 filter gain14.46
0No filtering.No filtering
1125 microseconds.125 us
2250 microseconds.250 us
3500 microseconds.500 us
41 millisecond.1 ms
52 milliseconds.2 ms
64 milliseconds.4 ms
77.9375 milliseconds.7.9375 ms
252 Parameters