EasyManua.ls Logo

ABB ACS880 - Page 253

ABB ACS880
764 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
0.100 s / real32(Visible when 14.1 Module 1 type = FAIO-01)
Defines the filter time constant for analog input AI2.
Unfiltered signal
Filtered signal
%
100
63
T
t
O = I × (1 - e
-t/T
)
I = filter input (step)
O = filter output
t
= time
T = filter time constant
Note: The signal is also filtered due to the signal
interface hardware. See parameter 14.46 AI2 filter gain.
AI2 filter time14.47
1000 = 1 s / 1000 = 1
s
Filter time constant.0.000 ... 30.000 s
0.000 mA or V /
real32
(Visible when 14.1 Module 1 type = FAIO-01)
Defines the minimum value for analog input AI2.
See also parameter 14.21 AI tune.
AI2 min14.48
1000 = 1 mA or V /
1000 = 1 mA or V
Minimum value of AI2.-22.000 ... 22.000 mA
or V
10.000 mA or V /
real32
(Visible when 14.1 Module 1 type = FAIO-01)
Defines the maximum value for analog input AI2.
See also parameter 14.21 AI tune.
AI2 max14.49
1000 = 1 mA or V /
1000 = 1 mA or V
Maximum value of AI2.-22.000 ... 22.000 mA
or V
Parameters 253

Table of Contents

Other manuals for ABB ACS880

Related product manuals