Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
12The start and stop commands are taken from fieldbus
adapter A.
Note: The start signal is always level-triggered with
this setting regardless of parameter 20.2 Ext1 start
trigger type.
Fieldbus A
14The start and stop commands are taken from the
embedded fieldbus interface.
Note: The start signal is always level-triggered with
this setting regardless of parameter 20.2 Ext1 start
trigger type.
Embedded fieldbus
15The start and stop commands are taken from another
drive through the master/follower link.
Note: The start signal is always level-triggered with
this setting regardless of parameter 20.2 Ext1 start
trigger type.
M/F link
21The start and stop commands are taken from the
application program control word (parameter 6.2
Application control word).
Note: The start signal is always level-triggered with
this setting regardless of parameter 20.2 Ext1 start
trigger type.
Application Program
22Reserved.ATF
16The start and stop commands are taken from an
external (DDCS) controller.
Note: The start signal is always level-triggered with
this setting regardless of parameter 20.2 Ext1 start
trigger type.
DDCS controller
Edge / uint16Defines whether the start signal for external control
location EXT1 is edge-triggered or level-triggered.
Note: This parameter is only effective when parameter
20.1 Ext1 commands is set to In1 Start, In1 Start; In2
Dir, In1 Start fwd; In2 Start rev, or Control panel.
Ext1 start trigger
type
20.2
0The start signal is edge-triggered.Edge
1The start signal is level-triggered.Level
DI1 / uint32Selects source 1 for parameter 20.1 Ext1 commands.Ext1 in1 source20.3
00 (always off).Not selected
11 (always on).Selected
2Digital input DI1 (10.2 DI delayed status, bit 0).DI1
3Digital input DI2 (10.2 DI delayed status, bit 1).DI2
4Digital input DI3 (10.2 DI delayed status, bit 2).DI3
5Digital input DI4 (10.2 DI delayed status, bit 3).DI4
Parameters 281