Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
6Digital input DI5 (10.2 DI delayed status, bit 4).DI5
7Digital input DI6 (10.2 DI delayed status, bit 5).DI6
10Digital input/output DIO1 (11.2 DIO delayed status, bit
0).
DIO1
11Digital input/output DIO2 (11.2 DIO delayed status, bit
1).
DIO2
See Terms and abbreviations (page 169).Other [bit]
DI2 / uint32Selects source 2 for parameter 20.1 Ext1 commands.
For the available selections, see parameter 20.3 Ext1
in1 source.
Ext1 in2 source20.4
Not selected / uint32Selects source 3 for parameter 20.1 Ext1 commands.
For the available selections, see parameter 20.3 Ext1
in1 source.
Ext1 in3 source20.5
Not selected / uint16Selects the source of start, stop and direction
commands for external control location 2 (EXT2).
See also parameters 20.720.10.
Ext2 commands20.6
0No start or stop command sources selected.Not selected
1The source of the start and stop commands is selected
by parameter 20.8 Ext2 in1 source. The state transitions
of the source bits are interpreted as follows:
CommandState of source 1 (20.8)
Start0?1 (20.7 =
Edge
)
1 (20.7 =
Level
)
Stop0
In1 Start
2The source selected by 20.8 Ext2 in1 source is the start
signal; the source selected by 20.9 Ext2 in2 source
determines the direction. The state transitions of the
source bits are interpreted as follows:
CommandState of source 2
(20.9)
State of source 1
(20.8)
StopAny0
Start forward00?1 (20.7 =
Edge
)
1 (20.7 =
Level
)
Start reverse1
In1 Start; In2 Dir
3The source selected by 20.8 Ext2 in1 source is the
forward start signal; the source selected by 20.9 Ext2
in2 source is the reverse start signal. The state
transitions of the source bits are interpreted as follows:
CommandState of source 2
(20.9)
State of source 1
(20.8)
Stop00
Start forward00?1 (20.7 =
Edge
)
1 (20.7 =
Level
)
Start reverse0?1 (20.7 =
Edge
)
1 (20.7 =
Level
)
0
Stop11
In1 Start fwd; In2
Start rev