Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
Coast (95.20 b10) /
uint16
Selects the way the motor is stopped when the run
enable signal switches off.
The source of the run enable signal is selected by
parameter 20.12 Run enable 1 source.
Run enable stop
mode
20.11
0Stop by switching off the output semiconductors of
the drive.
The motor coasts to a stop.
WARNING!
If a mechanical brake is used, ensure it is safe
to stop the drive by coasting.
Coast
1Stop along the active deceleration ramp. See parameter
group 23 Speed reference ramp (page 311).
Ramp
2Stop according to torque limits (parameters 30.19 and
30.20).
Torque limit
DIIL (95.20 b10);
Selected (95.20 b5);
DI5 (95.20 b9) /
uint32
Selects the source of the external run enable signal. If
the run enable signal is switched off, the drive will not
start. If already running, the drive will stop according
to the setting of parameter 20.11 Run enable stop
mode.
1 = Run enable signal on.
Note: The warning that indicates a missing signal can
be suppressed using parameter 20.30 Enable signals
warning function.
See also parameter 20.19 Enable start command.
Run enable 1 source20.12
00Not selected
11Selected
2Digital input DI1 (10.2 DI delayed status, bit 0).DI1
3Digital input DI2 (10.2 DI delayed status, bit 1).DI2
4Digital input DI3 (10.2 DI delayed status, bit 2).DI3
5Digital input DI4 (10.2 DI delayed status, bit 3).DI4
6Digital input DI5 (10.2 DI delayed status, bit 4).DI5
7Digital input DI6 (10.2 DI delayed status, bit 5).DI6
10Digital input/output DIO1 (11.2 DIO delayed status, bit
0).
DIO1
11Digital input/output DIO2 (11.2 DIO delayed status, bit
1).
DIO2
30Control word bit 3 received through fieldbus interface
A.
FBA A MCW bit 3
32Control word bit 3 received through the embedded
fieldbus interface.
EFB MCW bit 3
33DIIL input (10.2 DI delayed status, bit 15).DIIL
Parameters 285