Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
Inactive (true); DI4
(95.20 b1, 95.20 b2) /
uint32
Selects the source of the emergency stop signal. The
stop mode is selected by parameter 21.4 Emergency
stop mode.
0 = Emergency stop active
1 = Normal operation
Note: This parameter cannot be changed while the
drive is running.
Emergency stop
source
21.5
00.Active (false)
11.Inactive (true)
2DIIL input (10.2 DI delayed status, bit 15).DIIL
3Digital input DI1 (10.2 DI delayed status, bit 0).DI1
4Digital input DI2 (10.2 DI delayed status, bit 1).DI2
5Digital input DI3 (10.2 DI delayed status, bit 2).DI3
6Digital input DI4 (10.2 DI delayed status, bit 3).DI4
7Digital input DI5 (10.2 DI delayed status, bit 4).DI5
8Digital input DI6 (10.2 DI delayed status, bit 5).DI6
11Digital input/output DIO1 (11.2 DIO delayed status, bit
0).
DIO1
12Digital input/output DIO2 (11.2 DIO delayed status, bit
1).
DIO2
See Terms and abbreviations (page 169).Other [bit]
30.00 rpm / real32Defines the zero speed limit. The motor is stopped
along a speed ramp (when ramped stop is selected)
until the defined zero speed limit is reached. After the
zero speed delay, the motor coasts to a stop.
Note: If you use a value below the default, make sure
the drive is able to stop.
Zero speed limit21.6
- / -Zero speed limit. For scaling, see parameter 46.1.0.00 ... 30000.00
rpm
Parameters 293