Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
Not selected / uint32Selects the source of motor potentiometer up signal.
0 = No change
1 = Increase motor potentiometer value. (If both the up
and down sources are on, the potentiometer value will
not change.)
Motor
potentiometer up
source
22.73
00Not selected
11Selected
2Digital input DI1 (10.2 DI delayed status, bit 0).DI1
3Digital input DI2 (10.2 DI delayed status, bit 1).DI2
4Digital input DI3 (10.2 DI delayed status, bit 2).DI3
5Digital input DI4 (10.2 DI delayed status, bit 3).DI4
6Digital input DI5 (10.2 DI delayed status, bit 4).DI5
7Digital input DI6 (10.2 DI delayed status, bit 5).DI6
10Digital input/output DIO1 (11.2 DIO delayed status, bit
0).
DIO1
11Digital input/output DIO2 (11.2 DIO delayed status, bit
1).
DIO2
See Terms and abbreviations (page 169).Other [bit]
Not selected / uint32Selects the source of motor potentiometer down signal.
0 = No change
1 = Decrease motor potentiometer value. (If both the
up and down sources are on, the potentiometer value
will not change.)
For the selections, see parameter 22.73 Motor
potentiometer up source.
Motor
potentiometer down
source
22.74
60.0 s / real32Defines the change rate of the motor potentiometer.
This parameter specifies the time required for the
motor potentiometer to change from minimum (22.76)
to maximum (22.77). The same change rate applies in
both directions.
Motor
potentiometer ramp
time
22.75
10 = 1 s / 10 = 1 sMotor potentiometer change time.0.0 ... 3600.0 s
-1500.00 / real32Defines the minimum value of the motor potentiometer.Motor
potentiometer min
value
22.76
1 = 1 / 100 = 1Motor potentiometer minimum.-32768.00 ...
32767.00
1500.00 / real32Defines the maximum value of the motor
potentiometer.
Motor
potentiometer max
value
22.77
1 = 1 / 100 = 1Motor potentiometer maximum.-32768.00 ...
32767.00
- / real32Displays the output of the motor potentiometer
function. (The motor potentiometer is configured using
parameters 22.7122.74.)
This parameter is read-only.
Motor
potentiometer ref
act
22.80