Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
- / -High limit for critical frequency 2. For scaling, see
parameter 46.2.
-598.00 ... 598.00 Hz
0.00 Hz / real32Defines the low limit for critical frequency 3.
Note: This value must be less than or equal to the value
of 28.57 Critical frequency 3 high.
Critical frequency 3
low
28.56
- / -Low limit for critical frequency 3. For scaling, see
parameter 46.2.
-598.00 ... 598.00 Hz
0.00 Hz / real32Defines the high limit for critical frequency 3.
Note: This value must be greater than or equal to the
value of 28.56 Critical frequency 3 low.
Critical frequency 3
high
28.57
- / -High limit for critical frequency 3. For scaling, see
parameter 46.2.
-598.00 ... 598.00 Hz
Acc/Dec time 1 /
uint32
Selects a source that switches between the two sets
of acceleration/deceleration times defined by
parameters 28.7228.75.
0 = Acceleration time 1 and deceleration time 1 are in
force
1 = Acceleration time 2 and deceleration time 2 are in
force
Freq ramp set
selection
28.71
00.Acc/Dec time 1
11.Acc/Dec time 2
2Digital input DI1 (10.2 DI delayed status, bit 0).DI1
3Digital input DI2 (10.2 DI delayed status, bit 1).DI2
4Digital input DI3 (10.2 DI delayed status, bit 2).DI3
5Digital input DI4 (10.2 DI delayed status, bit 3).DI4
6Digital input DI5 (10.2 DI delayed status, bit 4).DI5
7Digital input DI6 (10.2 DI delayed status, bit 5).DI6
10Digital input/output DIO1 (11.2 DIO delayed status, bit
0).
DIO1
11Digital input/output DIO2 (11.2 DIO delayed status, bit
1).
DIO2
See Terms and abbreviations (page 169).Other [bit]
20.000 s / real32Defines acceleration time 1 as the time required for the
frequency to change from zero to the frequency defined
by parameter 46.2 Frequency scaling (not to parameter
30.14 Maximum frequency).
If the reference increases faster than the set
acceleration rate, the motor will follow the acceleration
rate.
If the reference increases slower than the set
acceleration rate, the motor frequency will follow the
reference.
If the acceleration time is set too short, the drive will
automatically prolong the acceleration in order not to
exceed the drive torque limits.
Freq acceleration
time 1
28.72