Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
1 = Signal selected by parameter 32.217 Supervision 5
signal is outside its limits.
Supervision 5 activeb4
1 = Signal selected by parameter 32.227 Supervision 6
signal is outside its limits.
Supervision 6 activeb5
1 = Signal selected by parameter 32.237 Supervision 7
signal is outside its limits.
Supervision 7 activeb6
Reservedb7…15
1 = 10000h…FFFFh
No action / uint16Selects the mode of signal supervision function 4.
Determines how the monitored signal (parameter
32.207 Supervision 4 signal) is compared to its lower
and upper limits (parameters 32.209 Supervision 4 low
and 32.310 Supervision 4 high respectively). The action
is taken when the condition is fulfilled as selected in
parameter 32.206 Supervision 4 action.
Supervision 4 action32.205
0Signal supervision 4 is not in use.Disabled
1A warning (D20B Signal supervision 4) is generated.Low
2Action is taken whenever the signal rises above its
upper limit.
High
3Action is taken whenever the absolute value of the
signal falls below its (absolute) lower limit.
Abs low
4Action is taken whenever the absolute value of the
signal rises above its (absolute) upper limit.
Abs high
5Action is taken whenever the signal falls below its low
limit or rises above its high limit.
Both
6Action is taken whenever the absolute value of the
signal falls below its (absolute) low limit or rises above
its (absolute) high limit.
Abs both
No action / uint16Selects the action the drive takes when the value
monitored by signal supervision 4 exceeds its limits.
Note: This parameter does not affect the status
indicated by 32.200 Supervision status.
Supervision 4 action32.206
0No action taken.No action
1A warning (D20B Signal supervision 4) is generated.Warning
2The drive trips on D103 Signal supervision 4.Fault
3If running, the drive trips on D103 Signal supervision 4.Fault if running
Zero / uint32Selects the signal to be monitored by signal supervision
function 4.
Supervision 4 signal32.207
0None.Zero
See Terms and abbreviations (page 169).Other [value]
0.000 s / real32Defines a filter time constant for the signal monitored
by signal supervision 4.
Supervision 4 filter
time
32.208
384 Parameters