Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
1000 = 1 s / 1000 = 1
s
Signal filter time.0.000 ... 30.000 s
0.00 / real32Defines the lower limit for signal supervision 4.Supervision 4 low32.209
- / -Low limit.-21474830.00 ...
21474830.00
0.00 / real32Defines the upper limit for signal supervision 4.Supervision 4 high32.310
- / -Upper limit.-21474830.00 ...
21474830.00
No action / uint16Selects the mode of signal supervision function 5.
Determines how the monitored signal (parameter 32.217
Supervision 5 signal) is compared to its lower and upper
limits (parameters 32.219 Supervision 5 low and 32.320
Supervision 5 high respectively). The action is taken
when the condition is fulfilled as selected in parameter
32.216 Supervision 5 action.
Supervision 5 action32.215
0Signal supervision 5 is not in use.Disabled
1A warning (D20C Signal supervision 5) is generated.Low
2Action is taken whenever the signal rises above its
upper limit.
High
3Action is taken whenever the absolute value of the
signal falls below its (absolute) lower limit.
Abs low
4Action is taken whenever the absolute value of the
signal rises above its (absolute) upper limit.
Abs high
5Action is taken whenever the signal falls below its low
limit or rises above its high limit.
Both
6Action is taken whenever the absolute value of the
signal falls below its (absolute) low limit or rises above
its (absolute) high limit.
Abs both
No action / uint16Selects the action that drive takes when the value
monitored by signal supervision 5 exceeds its limits.
Note: This parameter does not affect the status
indicated by 32.200 Supervision status.
Supervision 5 action32.216
0No action taken.No action
1A warning (D20C Signal supervision 5) is generated.Warning
2The drive trips on 80B2 Signal supervision 3.Fault
3If running, the drive trips on 80B2 Signal supervision 3.Fault if running
Zero / uint32Selects the signal to be monitored by signal supervision
function 5.
Supervision 5 signal32.217
0None.Zero
See Terms and abbreviations (page 169).Other [value]
0.000 s / real32Defines a filter time constant for the signal monitored
by signal supervision 5.
Supervision 5 filter
time
32.218