Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
1Constant 1.True
2Bit 0 of 10.21 RO status (page 214).RO1
See Terms and abbreviations (page 169).Other [bit]
On-time 2 exceeded
/ uint32
Selects the optional warning message for on-time timer
2.
On-time 2 warn
message
33.24
1A887 On-Time 2. The message text can be edited on
the control panel by choosing Menu – Settings – Edit
texts.
On-time 2 exceeded
6A88C Device clean.Clean device
7A890 Additional cooling fan.Maintain additional
cooling fan
8A88E Cabinet fan.Maintain cabinet fan
9A88D DC capacitor.Maintain DC
capacitors
10A880 Motor bearing.Maintain motor
bearing
- / uint32Actual present value of signal edge counter 1.
The counter is incremented every time the signal
selected by parameter 33.33 Edge counter 1 source
switches on or off (or either, depending on the setting
of 33.32 Edge counter 1 function). A divisor may be
applied to the count (see 33.34 Edge counter 1 divider).
When the counter exceeds the limit set by 33.31 Edge
counter 1 warn limit, bit 2 of 33.1 Counter status is set
to 1. The warning specified by 33.35 Edge counter 1
warn message is also given if enabled by 33.32 Edge
counter 1 function.
The counter can be reset from the Drive Composer PC
tool, or from the control panel by keeping Reset
depressed for over 3 seconds.
Edge counter 1
actual
33.30
- / -Actual present value of signal edge counter 1.0...4294967295
- / uint32Sets the warning limit for signal edge counter 1.Edge counter 1 warn
limit
33.31
- / -Warning limit for signal edge counter 1.0...4294967295
- / uint16Configures signal edge counter 1.Edge counter 1
function
33.32
0 = Loop: When the limit is reached, the counter is reset.
The counter status (bit 2 of 33.1) switches to 1 and
remains so until the counter is again incremented. The
warning (if enabled) stays active for at least 10 seconds.
1 = Saturate: When the limit is reached, the counter
status (bit 2 of 33.1) switches to 1, and remains so until
33.30 is reset. The warning (if enabled) also stays active
until 33.30 is reset.
Counter modeb0
0 = Disable: No warning is given when the limit is
reached
1 = Enable: A warning (see 33.35) is given when the limit
is reached
Warning enableb1
Parameters 391