Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
Count rising edges
0 = Disable: Rising edges are not counted
1 = Enable: Rising edges are counted
Count rising edgesb2
Count falling edges
0 = Disable: Falling edges are not counted
1 = Enable: Falling edges are counted
Count falling edgesb3
Reservedb4…15
1 = 10000h…FFFFh
False / uint32Selects the signal to be monitored by signal edge
counter 1.
Edge counter 1
source
33.33
0Constant 0.False
1Constant 1.True
2Bit 0 of 10.21 RO status (page 214).RO1
See Terms and abbreviations (page 169).Other [bit]
1 / uint32Defines a divisor for signal edge counter 1. Determines
how many signal edges increment the counter by 1.
Edge counter 1
divider
33.34
- / -Divisor for signal edge counter 1.1...2147483647
Edge counter 1
exceeded / uint32
Selects the optional warning message for signal edge
counter 1.
Edge counter 1 warn
message
33.35
2A888 Edge counter 1. The message text can be edited
on the control panel by choosing Menu Settings Edit
texts.
Edge counter 1
exceeded
11A884 Main contactor.Counted main
contactor
12A881 Output relay.Counted output
relay
13A882 Motor starts.Counted motor
starts
14A883 Power ups.Counted power ups
15A885 DC charge.Counted DC charges
- / uint32Displays the actual present value of signal edge counter
2.
The counter is incremented every time the signal
selected by parameter 33.43 Edge counter 2 source
switches on or off (or either, depending on the setting
of 33.42 Edge counter 2 function). A divisor may be
applied to the count (see 33.44 Edge counter 2 divider).
When the counter exceeds the limit set by 33.41 Edge
counter 2 warn limit, bit 3 of 33.1 Counter status is set
to 1. The warning specified by 33.45 Edge counter 2
warn message is also given if enabled by 33.42 Edge
counter 2 function.
The counter can be reset from the Drive Composer PC
tool, or from the control panel by keeping Reset
depressed for over 3 seconds.
Edge counter 2
actual
33.40
- / -Actual present value of signal edge counter 2.0...4294967295
392 Parameters