Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
- / uint32Sets the warning limit for signal edge counter 2.Edge counter 2 warn
limit
33.41
- / -Warning limit for signal edge counter 2.0...4294967295
- / uint16Configures signal edge counter 2.Edge counter 2
function
33.42
0 = Loop: When the limit is reached, the counter is reset.
The counter status (bit 3 of 33.1) remains 1 until the
counter is again incremented. The warning (if enabled)
stays active for at least 10 seconds.
1 = Saturate: After the limit is reached, the counter
status (bit 3 of 33.1) remains 1 until 33.40 is reset. The
warning (if enabled) also stays active until 33.40 is
reset.
Counter modeb0
Warning enable
0 = Disable: No warning is given when the limit is
reached
1 = Enable: A warning (see 33.45) is given when the limit
is reached
Warning enableb1
Count rising edges
0 = Disable: Rising edges are not counted
1 = Enable: Rising edges are counted
Count rising edgesb2
Count falling edges
0 = Disable: Falling edges are not counted
1 = Enable: Falling edges are counted
Count falling edgesb3
Reservedb4…15
1 = 10000h…FFFFh
False / uint32Selects the signal to be monitored by signal edge
counter 2.
Edge counter 2
source
33.43
00.False
11.True
2Bit 0 of 10.21 RO status (page 214).RO1
See Terms and abbreviations (page 169).Other [bit]
1 / uint32Defines a divisor for signal edge counter 2. Determines
how many signal edges increment the counter by 1.
Edge counter 2
divider
33.44
- / -Divisor for signal edge counter 2.1...4294967295
Edge counter 2
exceeded / uint32
Selects the optional warning message for signal edge
counter 2.
Edge counter 2 warn
message
33.45
3A889 Edge counter 2. The message text can be edited
on the control panel by choosing Menu – Settings – Edit
texts.
Edge counter 2
exceeded
11A884 Main contactor.Counted main
contactor
12A881 Output relay.Counted output
relay
13A882 Motor starts.Counted motor
starts
Parameters 393